They are intended for an insulation and mounting of the current-carrying parts in electrical devices, switchgears of power stations and substations. They are used for the packaging of: disconnect switches of indoor installation, circuit breakers, power cabinets, safety cutoffs, for tire insulation. The material of the insulating part is a ceramic electrotechnical material of a subgroup 110 GOST 20419-83. They meet the requirements of TU 16-528.105-77.
| Insulator name* |
Designation of the drawing |
GOST, TU |
Voltage class, kV |
The length of insulation distance is not less than, cm |
N, mm |
D outer, mm |
Weight, kg |
Rough drawing |
| nom. |
prev. deviation + -10% |
| ИО-1-2,5-1 У3 |
INYAZH.686111.005SB |
TU U26.2-00214652-002:2010 |
1 |
— |
60 |
70 |
0,53 |
0,053 |
 |
| ИОов-1-7,5-1 У3 |
INYAZH.686111.004SB |
TU U 26.2-00214652-002: 2010 |
1 |
— |
70 |
174 |
1,5 |
0,15 |
 |
| ИО-6-3,75 I У3 ИО-6-3,75 II У3 |
INYAZH.686112.003SB |
GOST 9984-85 |
6 |
— |
100 |
77 |
1,0 |
0,1 |
 |
| ИО-10-3,75 I У3 ИО-10-3,75 II У3 |
INYAZH.686113.007SB |
GOST 9984-85 |
10 |
— |
120 |
82 |
1,4 |
0,14 |
 |
| ИО-10-20,00 У3 |
INYAZH.686113.005SB |
GOST 9984-85 |
10 |
— |
134 |
160 |
6,0 |
0,6 |
 |
| OFR-10-7,5-II UHL2 |
INYUM.686113.011SB |
GOST 9984-85 |
10 |
17,5 |
190 |
220 |
5,5 |
0,55 |
 |
| OFR-20-7,5-II UHL2 |
INYAZH.686114.006SB |
GOST 9984-85 |
20 |
40 |
257 |
220 |
8,3 |
0,83 |
 |
| OFR-35-4-II UHL2 |
BFIR.686115.015SB |
GOST 9984-85 |
35 |
60 |
356 |
220 |
14,6 |
1,46 |
 |
| I4-80 I UHL2 |
ИМЖК.686113.018SB |
GOST 9984-85 |
10 |
— |
120 |
105 |
2,10 |
0,21 |
 |
| I4-60 IІ UHL2 |
IMZHK.686112.015SB |
GOST 9984-85 |
6 |
— |
95 |
85 |
1,20 |
0,12 |
 |
| I4-60 III UHL2 |
IMZHK.686112.015SB |
GOST 9984-85 |
6 |
— |
100 |
85 |
1,20 |
0,12 |
 |
| IOR-10-7,50 I UHL2 |
INYAZH.686113.006SB |
GOST 9984-85 |
10 |
— |
124 |
115 |
2,90 |
0,29 |
 |
| IOR-10-7,50 III UHL2 |
NIYUD.686113.014SB |
GOST 9984-85 |
10 |
18 |
120 |
115 |
2,5 |
0,25 |
 |
| IOR-10-7,50 III-1 UHL2 |
NIYUD.686113.010SB |
GOST 9984-85 |
10 |
— |
124 |
115 |
2,88 |
0,28 |
 |
| IOR-6-1,0 UHL2 |
NIYUD.384SB |
GOST 9984-85 |
6 |
— |
70 |
78 |
0,65 |
0,06 |
 |
| IOR-6-3,75 UHL2 |
INSHYU.686112.006SB |
GOST 9984-85 |
6 |
— |
100 |
84 |
1,10 |
0,11 |
 |
| IOR-10-3,75 UHL2 |
ILYUT.686113.003SB |
GOST 9984-85 |
10 |
— |
120 |
96 |
1,60 |
0,16 |
 |
| IOR-20-7,50 У3 |
INYAZH.686114.003SB |
GOST 9984-85 |
20 |
— |
160 |
160 |
6,30 |
0,63 |
 |
| IOR-24-6 UHL2 |
ILYAN.686115.025SB |
GOST 9984-85 |
24 |
48 |
307 |
220 |
9,7 |
0,97 |
 |
| IORF-20-8,0 І UHL2 |
NIYUD.686143.022SB |
GOST 9984-85 |
20 |
40 |
232 |
198 |
7,1 |
0,71 |
 |
| IORF-20-8,0 ІІ UHL2 |
NIYUD.686143.022-01SB |
GOST 9984-85 |
20 |
50 |
272 |
198 |
8,1 |
0,81 |
 |
| IORF-24-8,0 UHL2 |
NIYUD.686143.022-02SB |
GOST 9984-85 |
24 |
62 |
302 |
198 |
9,3 |
0,93 |
 |
The following letters and figures in the conventional value of IOR and OFR insulator types denote:
I – insulator;
O – supporting;
R – ribbed;
F – porcelain;
1; 6; 10; 20; 24; 35 – nominal voltage, kV;
1; 2.5; 3.75; 4; 6; 7.5; 20 – minimum breaking force while bending (breaking), kN;
60; 80 – impulse test voltage, kV;
I; II; III; IV – hardware versions;
UHL – climatic version according to GOST 15150-69;
2 (under the covers); 3 (indoors) – placement (operation) category according to GOST 15150-69.
The following letters and figures in the conventional value of IO and IOov insulator types denote:
I – insulator;
O – supporting;
ov – oval shaped base stand;
1 – nominal voltage, kV;
2,5; 7,5 – minimum breaking force while bending (breaking), kN;
1 – modification;
U – climatic version according to GOST 15150-69;
3 (indoors) – placement (operation) category according to GOST 15150-69.
The following letters and figures in the conventional value of I4 and I8 insulator types denote:
I – insulator;
4; 8 – minimum breaking force while bending (breaking), kN;
60; 80; 125 – test voltage of lightning impulse;
UHL – climatic version according to GOST 15150-69;
2 – placement category according to GOST 15150-69.